EMACSA (Empresa Municipal de Aguas de Córdoba, S.A.) is a Spanish public company responsible for managing the integrated water service in the city of Córdoba, Spain, in the autonomous community of Andalusia.
IREM S.p.A., in collaboration with its Spanish distributor SALTOS DEL PIRINEO, has implemented a hydroelectric energy recovery installation at the Villa Azul drinking water treatment plant (ETAP) in Córdoba.
Water reaches the inlet of the plant with a residual pressure of 2.4 bar and a flow rate of 556 l/s. Previously, this energy was entirely lost through a regulating valve, being dissipated without being utilised. Today, that same pressure, through the installation of an IREM hydroelectric turbine, directly supplies some of the plant’s own operations.
This is not the first time that IREM has carried out a project of this type. The Villa Azul plant joins other facilities where similar systems have been implemented – both in drinking water treatment plants (ETAP) and wastewater treatment plants (EDAR) – recovering pressure drops that were previously regulated without generating even one kWh.
For the plant in question, an IREM Banki cross-flow turbine-generator unit with an electrical output of 93 kW and standalone connection, model TBS4-1,1, has been installed.
The turbine operates in standalone mode with a regulation system that ensures frequency stability through the use of nine IREM RMP 12/B electronic regulators, which dissipate excess energy, allowing extremely precise load regulation.
The IREM system for standalone hydroelectric plants is known for providing a reliable and easy-to-install solution, capable of generating electrical energy with a high level of power quality.
The operating principle of IREM components for standalone plants is based on the so-called “constant load” method.
The electronic regulators, combined with the distribution and automation switchboard, regulate the required network frequency (50 or 60 Hz) in real time, achieving a perfect balance between the power generated by the hydroelectric turbine and the power used by the loads.
The IREM turbine-switchboard-regulator system has been designed according to the principles of reliability, efficiency and simplicity. This design philosophy has made it possible to achieve high-efficiency plants requiring very low maintenance, which are easy to install and manage.